Concord 48
Siren Options Menu
The SIREN OPTIONS menu lets you set up siren operation and supervision.
The following describes how to program the siren option settings that appear under
GLOBAL.
System Tamper (partition 1: 06109, partition 2: 06209)
Reporting-Partition 1-2 (Default = off)
This setting determines how the panel handles possible tamper situations. When
this feature is on, the panel reacts in the following two ways:
• The system goes into alarm if several attempts are made to disarm the sys-
tem with incorrect access codes (40 consecutive keypresses).
• The panel reports to the central station if a bus device stops communicating
with the panel.
Note
For UL Commercial Listed installations (UL 1610), System Tamper must be set to on.
¾To change the System Tamper setting:
1. With the display showing SYSTEM
TAMPER OFF/ON
(current setting),
press 1 (off) or 2 (on). The display
flashes the entered setting.
2. Press # and the display shows the new
setting.
Immediate Beeps (0700)
Siren Options-Global (Default = off)
This setting determines whether the panel activates trouble beeps as
soon as a wireless device supervisory condition is detected (on), or if
the panel waits until “supervisory time” to activate trouble beeps (off).
(Refer to
TIMERS—GLOBAL—SUPERVISORY TIME).
Note
For UL Listed installations, this feature must be on.
¾To turn Immediate Beeps off or on:
1. With the display showing IMMEDIATE BEEPS
OFF/ON
(current setting), press 1 (off) or 2 (on).
The display flashes the entered setting.
2. Press # and the display shows the new setting.
Disable Trouble Beeps (0701)
Siren Options-Global (Default = off)
When this setting is on, the panel will not beep to alert users of wire-
less device supervisory trouble.
Note
For UL Listed installations, Disable Trouble Beeps must be set to off.
¾To turn Disable Trouble Beeps off or on:
1. With the display showing DISABLE TR BEEPS
OFF/ON
(current setting), press 1 (off) or 2 (on).
The display flashes the entered setting.
2. Press # and the display shows the new setting.
UL 98 Options (0702)
Siren Options-Global (Default = off)
This setting determines whether the panel complies with UL 98
requirements (4-hour trouble beep restart, 4-hour backup battery test,
4-hour smoke (group 26) zone supervisory).
Note
For UL Listed installations, this feature must be on.
¾To turn UL 98 Options off or on:
1. With the display showing UL 98 OPTIONS OFF/ON
(current setting), press 1 (off) or 2 (on). The dis-
play flashes the entered setting.
2. Press # and the display shows the new setting.