GE Power Management
735/737 Feeder Protection Relay 4-15
4 MODBUS COMMUNICATIONS 4.3 MEMORY MAP
4
F110
continued
60 = 11
65 = 12
70 = 13
75 = 14
80 = 15
85 = 16
90 = 17
95 = 18
100 = 19
F111 GROUND INST DIAL OFF = 1
0.1 = 2
0.2 = 3
0.4 = 4
0.8 = 5
1 = 6
2 = 7
4 = 8
8 = 9
16 = 10
F112 TIME MULTIPLIER DIAL 1 = 1
2 = 2
3 = 3
4 = 4
5 = 5
6 = 6
7 = 7
8 = 8
9 = 9
10 = 10
F113 CAUSE OF TRIP XXXX XXXX XXXX XXX1 = Phase A time OC trip
XXXX XXXX XXXX XX1X = Phase B time OC trip
XXXX XXXX XXXX X1XX = Phase C time OC trip
XXXX XXXX XXXX 1XXX = Ground time OC trip
XXXX XXXX XXX1 XXXX = Phase A inst trip
XXXX XXXX XX1X XXXX = Phase B inst trip
XXXX XXXX X1XX XXXX = Phase C inst trip
XXXX XXXX 1XXX XXXX = Ground inst trip
Table 4–2: 735/737 MEMORY MAP DATA FORMATS (Sheet 4 of 5)
FORMAT TYPE DESCRIPTION