AN-24 Terminal 54 Low Ref./Feedb. Value
Range: Function:
0 Unit* [-1000000.000 to par. AN-25] Enter the analog input scaling value that corresponds to the minimum reference feedback value set in
par. F-52 Minimum Reference.
AN-25 Terminal 54 High Ref./Feedb. Value
Range: Function:
1500.000
Unit*
[Par. AN-24 to 1000000.000] Enter the analog input scaling value that corresponds to the maximum reference feedback value set in
par. F-53 Maximum Reference.
AN-26 Terminal 54 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s] Enter the time constant. This is a first-order digital low pass filter time constant for suppressing electrical
noise in terminal 54. A high time constant value improves dampening but also increases the time delay
through the filter.
This parameter cannot be adjusted while the motor is running.
3.8.4 AN-3# Analog Input X30/11
Parameters to configure the scaling and limits for Analog Input 1 associated with OPCGPIO General Purpose Field Installed Option Module.
AN-30 Terminal X30/11 Low Voltage
Range: Function:
0.07 V* [0.00 - par. AN-31 V] Sets the analog input scaling value to correspond to the low reference/feedback value (set in par.
AN-34 Term. X30/11 Low Ref./Feedb. Value).
AN-31 Terminal X30/11 High Voltage
Range: Function:
10.00 V* [par. AN-30 - 10.00 V] Sets the analog input scaling value to correspond to the high reference/feedback value (set in par.
AN-35 Term. X30/11 High Ref./Feedb. Value).
AN-34 Term. X30/11 Low Ref./Feedb. Value
Range: Function:
0.000 Unit* [-1000000.000 to par. AN-35] Sets the analog input scaling value to correspond to the low voltage value (set in par. AN-30 Terminal
X30/11 Low Voltage).
AN-35 Term. X30/11 High Ref./Feedb. Value
Range: Function:
1500.000* [Par. AN-34 to 1000000.000] Sets the analog input scaling value to correspond to the high voltage value (set in par. AN-31 Terminal
X30/11 High Voltage).
AN-36 Term. X30/11 Filter Time Constant
Range: Function:
0.001 s* [0.001 - 10.000 s]
A 1
st
order digital low pass filter time constant for suppressing electrical noise on terminal X30/11.
par. AN-36 Term. X30/11 Filter Time Constant cannot be changed while the motor is running.
3.8.5 AN-4# Analog Input X30/12
Parameters to configure the scaling and limits for Analog Input 2 associated with OPCGPIO General Purpose Field Installed Option Module.
AF-650 GP Programming Guide
102