Bit: Meaning:
0 Connection with DP-master is not ok
1Not used
2 FDL (Field-bus Data link Layer) is not ok
3 Clear data command received
4 Actual value is not updated
5 Baudrate search
6 PROFIBUS ASIC is not transmitting
7 Initializing of PROFIBUS is not ok
8 Frequency converter is tripped
9 Internal CAN error
10 Wrong configuration data from PLC
11 Wrong ID sent by PLC
12 Internal error occured
13 Not configured
14 Timeout active
15 Warning 34 active
PB-63 Actual Baud Rate
Option: Function:
This parameter displays the actual Profibus baud rate. The Profibus Master automatically sets the baud
rate.
[0] 9,6 kbit/s
[1] 19,2 kbit/s
[2] 93,75 kbit/s
[3] 187,5 kbit/s
[4] 500 kbit/s
[6] 1500 kbit/s
[7] 3000 kbit/s
[8] 6000 kbit/s
[9] 12000 kbit/s
[10] 31,25 kbit/s
[11] 45,45 kbit/s
[255] * No baudrate found
PB-64 Device Identification
Range: Function:
0* [] This parameter displays the device identification. Please refer to the Operating Instructions for Profibus,
for further explanation.
PB-65 Profile Number
Range: Function:
0* [] This parameter contains the profile identification. Byte 1 contains the profile number and byte 2 the
version number of the profile.
NB!
This parameter is not visible via Keypad.
PB-67 Control Word 1
Range: Function:
0* [0 - 65535] This parameter accepts the Control Word from a Master Class 2 in the same format as PCD 1.
PB-68 Status Word 1
Range: Function:
0* [0 - 65535] This parameter delivers the Status Word for a Master Class 2 in the same format as PCD 2.