K-12 This Set-up Linked to
Option: Function:
To enable conflict-free changes from one set-up to another during operation, link set-ups containing
parameters which are not changeable during operation. The link will ensure synchronising of the ‘not
changeable during operation’ parameter values when moving from one set-up to another during oper-
ation. ‘Not changeable during operation’ parameters can be identified by the label FALSE in the parameter
lists in the section Parameter Lists.
par. K-12 This Set-up Linked to is used by Multi set-up in par. K-10 Active Set-up. Multi set-up is used to
move from one set-up to another during operation (i.e. while the motor is running).
Example:
Use Multi set-up to shift from Set-up 1 to Set-up 2 whilst the motor is running. Program in Set-up 1 first,
then ensure that Set-up 1 and Set-up 2 are synchronised (or ‘linked’). Synchronisation can be performed
in two ways:
1. Change the edit set-up to Set-up 2 [2] in par. K-11 Edit Set-up and set par. K-12 This Set-up Linked to to
Set-up 1 [1]. This will start the linking (synchronising) process.