E-81 Term 32/33 Encoder Direction
Option: Function:
Change the detected encoder rotation direction without changing the wiring to the encoder.
[0] * Clockwise Sets channel A 90° (electrical degrees) behind channel B upon clockwise rotation of the encoder shaft.
[1] Counter clockwise Sets channel A 90° (electrical degrees) ahead of channel B upon clockwise rotation of the encoder shaft.
This parameter cannot be adjusted while the motor is running.
3.4.8 E-9# Bus Controlled
Parameters to configure digital, relay and pulse train outputs to be controlled by the serial communications.
E-90 Digital & Relay Bus Control
Range: Function:
0* [0 - FFFFFFFF] This parameter holds the state of the digital outputs and relays that is controlled by bus.
A logical '1' indicates that the output is high or active.
A logical '0' indicates that the output is low or inactive.
Bit 0
Digital Output Terminal 27
Bit 1 Digital Output Terminal 29
Bit 2 Digital Output Terminal X 30/6
Bit 3 Digital Output Terminal X 30/7
Bit 4 Relay 1 output terminal
Bit 5 Relay 2 output terminal
Bit 6 Option B Relay 1 output terminal
Bit 7 Option B Relay 2 output terminal
Bit 8 Option B Relay 3 output terminal
Bit 9-15 Reserved for future terminals
Bit 16 Option C Relay 1 output terminal
Bit 17 Option C Relay 2 output terminal
Bit 18 Option C Relay 3 output terminal
Bit 19 Option C Relay 4 output terminal
Bit 20 Option C Relay 5 output terminal
Bit 21 Option C Relay 6 output terminal
Bit 22 Option C Relay 7 output terminal
Bit 23 Option C Relay 8 output terminal
Bit 24-31 Reserved for future terminals
E-93 Pulse Out #27 Bus Control
Range: Function:
0.00 %* [0.00 - 100.00 %] Set the output frequency transferred to the output terminal 27 when the terminal is configured as 'Bus
Controlled' in par. E-70 Terminal 27 Pulse Output Variable [45].
E-94 Pulse Out #27 Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00 %] Set the output frequency transferred to the output terminal 27 when the terminal is configured as 'Bus
Ctrl Timeout' in par. E-70 Terminal 27 Pulse Output Variable [48]. And a time-out is detected.
E-95 Pulse Out #29 Bus Control
Range: Function:
0.00 %* [0.00 - 100.00 %] Set the output frequency transferred to the output terminal 29 when the terminal is configured as 'Bus
Controlled' in par. E-70 Terminal 27 Pulse Output Variable [45].
E-96 Pulse Out #29 Timeout Preset
Range: Function:
0.00 %* [0.00 - 100.00 %] Set the output frequency transferred to the output terminal 29 when the terminal is configured as 'Bus
Ctrl Timeout' in par. E-70 Terminal 27 Pulse Output Variable [48]. And a time-out is detected.