[48] Bus ctrl., timeout
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor Current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
[119] Torque % lim
E-75 Terminal X30/6 Pulse Output Variable
Option: Function:
[0] * No operation Select the variable for read-out on terminal X30/6.
This parameter cannot be adjusted while the motor is running.
This parameter is active when the General Purpose I/O Option Module (OPCGPIO) is installed in the fre-
quency converter.
[45] Bus ctrl.
[48] Bus ctrl., timeout
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor Current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[113] Ext. Closed Loop 1
[114] Ext. Closed Loop 2
[115] Ext. Closed Loop 3
E-78 Pulse Output Max Freq #X30/6
Range: Function:
5000. Hz* [0 - 32000 Hz] Select the maximum frequency on terminal X30/6 referring to the output variable in par. E-75 Terminal
X30/6 Pulse Output Variable. This parameter cannot be adjusted while the motor is running.
This parameter is active when the General Purpose I/O Option Module (OPCGPIO) is mounted in the fre-
quency converter.
3.4.7 E-8# 24V Encoder Input
Parameters to configure the Encoder outputs.
E-80 Term 32/33 Pulses Per Revolution
Range: Function:
1024 PPR* [128 - 4096 PPR] Set the encoder pulses per revolution on the motor shaft. Read the correct value from the encoder.
This parameter cannot be adjusted while the motor is running.
AF-650 GP Programming Guide
78
3