E-67 Term. 33 Low Ref./Feedb. Value
Range: Function:
0.000* [-999999.999 - 999999.999] Enter the low reference value [RPM] for the motor shaft speed. This is also the low feedback value, see
also par. E-62 Term. 29 Low Ref./Feedb. Value.
E-68 Term. 33 High Ref./Feedb. Value
Range: Function:
1500.000
Unit*
[-999999.999 - 999999.999] Enter the high reference value [RPM] for the motor shaft speed. See also par. E-63 Term. 29 High Ref./
Feedb. Value.
E-69 Pulse Filter Time Constant #33
Range: Function:
100 ms* [1 - 1000 ms] Enter the pulse filter time constant. The low-pass filter reduces the influence on and dampens oscillations
on the feedback signal from the control.
This is an advantage, e.g. if there is a great amount on noise in the system. This parameter cannot be
adjusted while the motor is running.
3.4.6 E-7# Pulse Output
Parameters to configure terminal 27 and 29 as Pulse Train Outputs and to configure Encoder input terminals 32 and 33.
E-70 Terminal 27 Pulse Output Variable
Option: Function:
[0] * No operation Select the desired display output for terminal 27.
This parameter cannot be adjusted while the motor is running.
[45] Bus ctrl.
[48] Bus ctrl., timeout
[100] Output frequency
[101] Reference
[102] Feedback
[103] Motor Current
[104] Torque rel to limit
[105] Torq relate to rated
[106] Power
[107] Speed
[108] Torque
[109] Max Out Freq
[119] Torque % lim
E-72 Pulse Output Max Freq #27
Range: Function:
5000. Hz* [0 - 32000 Hz] Set the maximum frequency for terminal 27, corresponding to the output variable selected in par.
E-70 Terminal 27 Pulse Output Variable.
This parameter cannot be adjusted while the motor is running.
E-73 Terminal 29 Pulse Output Variable
Option: Function:
[0] * No operation Select the desired display output for terminal 29.
This parameter cannot be adjusted while the motor is running.
[45] Bus ctrl.
AF-650 GP Programming Guide
77