[85] Logic Controller digital output F
[120] Local ref active
[121] Remote ref active
[122] No alarm
[123] Start command activ
[124] Running reverse
[125] Drive in hand mode
[126] Drive in auto mode
3.4.5 E-6# Pulse Input
Parameters to configure terminal 29 and 33 as Pulse Train inputs.
E-60 Term. 29 Low Frequency
Range: Function:
100 Hz* [0 - 110000 Hz] Enter the low frequency limit corresponding to the low motor shaft speed (i.e. low reference value) in par.
E-62 Term. 29 Low Ref./Feedb. Value. Refer to the diagram in this section.
E-61 Term. 29 High Frequency
Range: Function:
100 Hz* [0 - 110000 Hz] Enter the high frequency limit corresponding to the high motor shaft speed (i.e. high reference value) in
par. E-63 Term. 29 High Ref./Feedb. Value.
E-62 Term. 29 Low Ref./Feedb. Value
Range: Function:
0.000 Unit* [-999999.999 - 999999.999] Enter the low reference value limit for the motor shaft speed [RPM]. This is also the lowest feedback value,
see also par. E-67 Term. 33 Low Ref./Feedb. Value. Set terminal 29 to digital input (par. E-52 Terminal 29
Mode =input [0] (default) and par. E-04 Terminal 29 Digital Input = applicable value).
E-63 Term. 29 High Ref./Feedb. Value
Range: Function:
1500.000
Unit*
[-999999.999 - 999999.999] Enter the high reference value [RPM] for the motor shaft speed and the high feedback value, see also
par. E-68 Term. 33 High Ref./Feedb. Value. Select terminal 29 as a digital input (par. E-52 Terminal 29
Mode =input [0] (default) and par. E-04 Terminal 29 Digital Input = applicable value).
E-64 Pulse Filter Time Constant #29
Range: Function:
100 ms* [1 - 1000 ms] Enter the pulse filter time constant. The pulse filter dampens oscillations of the feedback signal, which is
an advantage if there is a lot of noise in the system. A high time constant value results in better dampening
but also increases the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
E-65 Term. 33 Low Frequency
Range: Function:
100 Hz* [0 - 110000 Hz] Enter the low frequency corresponding to the low motor shaft speed (i.e. low reference value) in par.
E-67 Term. 33 Low Ref./Feedb. Value.
E-66 Term. 33 High Frequency
Range: Function:
100 Hz* [0 - 110000 Hz] Enter the high frequency corresponding to the high motor shaft speed (i.e. high reference value) in par.
E-68 Term. 33 High Ref./Feedb. Value.