5-24 B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP CHAPTER 5: SETTINGS
5
With the graphical front panel, the language can be changed regardless of the language purchased. That is, all languages 
can be used. If you select a language with which you are unfamiliar and want to switch back to English for example, the 
menu order remains the same. That is, Settings is always second, Product Setup is always first, Display Properties is always 
second, and Language is always first.
The language can be selected also for the front panel in EnerVista under Maintenance > Change Front Panel.
The language of the EnerVista software can be changed under View > Language.
FLASH MESSAGE TIME — Flash messages are status, warning, error, and information messages displayed in response to 
certain key presses during settings programming. These messages override any normal messages. Use this setting to 
change the duration of flash messages on the display.
DEFAULT MESSAGE TIMEOUT — If the keypad is inactive for a period of time, the relay automatically reverts to a default 
message. The inactivity time is modified using this setting to ensure that messages remain on the screen long enough 
during programming or reading of actual values. This setting is not supported on the graphical front panel.
DEFAULT MESSAGE INTENSITY — To extend phosphor life in the vacuum fluorescent display, the brightness can be 
attenuated during default message display. During keypad interrogation, the display always operates at full brightness. 
This setting is not supported on the graphical front panel.
SCREEN SAVER FEATURE and SCREEN SAVER WAIT TIME — These settings are only visible if the B90 has a liquid crystal display 
(LCD) and control its backlighting. When the 
SCREEN SAVER FEATURE is “Enabled,” the LCD backlighting turns off after the 
DEFAULT MESSAGE TIMEOUT followed by the SCREEN SAVER WAIT TIME, provided that no keys have been pressed and no 
target messages are active. When a keypress occurs or a target becomes active, the LCD backlighting turns on. These 
settings are not supported on the graphical front panel.
CURRENT CUT-OFF LEVEL — This setting modifies the current cut-off threshold. Very low currents (1 to 2% of the rated value) 
are very susceptible to noise. Some customers prefer very low currents to display as zero, while others prefer the current to 
display even when the value reflects noise rather than the actual signal. The B90 applies a cut-off value to the magnitudes 
and angles of the measured currents. If the magnitude is below the cut-off level, it is substituted with zero. This applies to 
phase and ground current phasors as well as true RMS values and symmetrical components. The cut-off operation applies 
to quantities used for metering, protection, and control, as well as those used by communications protocols. Note that the 
cut-off level for the sensitive ground input is 10 times lower that the 
CURRENT CUT-OFF LEVEL setting value. Raw current 
samples available via oscillography are not subject to cut-off.
VOLTAGE CUT-OFF LEVEL — This setting modifies the voltage cut-off threshold. Very low secondary voltage measurements 
(at the fractional volt level) can be affected by noise. Some customers prefer these low voltages to be displayed as zero, 
while others prefer the voltage to be displayed even when the value reflects noise rather than the actual signal. The B90 
applies a cut-off value to the magnitudes and angles of the measured voltages. If the magnitude is below the cut-off level, 
it is substituted with zero. This operation applies to phase and auxiliary voltages, and symmetrical components. The cut-off 
operation applies to quantities used for metering, protection, and control, as well as those used by communications 
protocols. Raw samples of the voltages available via oscillography are not subject to cut-off.
5.3.4  Graphical front panel
Use the EnerVista software to configure the graphical front panel. The settings are not accessible from the graphical front 
panel.
The following screens are available:
• Home page
Lower the 
VOLTAGE CUT-OFF LEVEL and CURRENT CUT-OFF LEVEL with care as the relay accepts lower signals as valid 
measurements. Unless dictated otherwise by a specific application, the default settings of “0.02 pu” for CURRENT 
CUT-OFF LEVEL 
and “1.0 V” for VOLTAGE CUT-OFF LEVEL are recommended.
The graphical front panel is a hardware option. See the Order Codes section in chapter 2 for details.