6-12 B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
RECORDS CHAPTER 6: ACTUAL VALUES
6
This menu displays the user-programmable fault report actual values. See the User-Programmable Fault Report section in 
chapter 5 for information on this feature.
6.5.2  Event records
6.5.2.1  Enhanced and standard front panels
ACTUAL VALUES  RECORDS  EVENT RECORDS
The event records menu shows the contextual data associated with up to the last 1024 events, listed in chronological 
order from most recent to oldest. When all 1024 event records have been filled, the oldest record is removed as a new 
record is added. Each event record shows the event identifier/sequence number, cause, and date/time stamp associated 
with the event trigger. See the 
COMMANDS  CLEAR RECORDS menu for clearing event records.
Only major output operands generate events, not every operand. Elements that assert output per phase, for example, log 
operating phase output only without asserting the common three-phase operand event.
See also the system log (syslog) information in the previous chapter.
The event records are also viewable in the software and in a web browser. The figure shows the event records in the 
software. To view them in a web browser, enter the IP address of the device. When an oscillography icon displays, click it to 
open it.
Figure 6-3: Event records viewed in EnerVista software
LAST REPORT DATE:
2002/10/09 08:25:27
 EVENT RECORDS
EVENT: XXX
XXX
Date and time stamps
EVENT: 3
POWER ON
EVENT 3
DATE: 2000/07/14
EVENT: 2
POWER OFF
EVENT 3
TIME: 14:53:00.03405
EVENT: 1
EVENTS CLEARED