CHAPTER 5: SETTINGS PRODUCT SETUP
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-87
5
Commands
The UR implements a number of clear records commands as detailed in the Commands and Targets chapter of this
manual. Several of these commands also can be issued via IEC 61850. The settings related to these IEC 61850 commands
are described here.
Navigate to Settings > Product Setup > Communications > IEC 61850 > Settings for Commands to access the settings
that configure the IEC 61850 protocol interface for record clear commands.
Figure 5-40: Commands panel
FltRptRFLO1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"
here is select-before-operate. Enhanced security means that the B90 reports to the client the breaker 1 position at the
end of the command sequence.
LLN0.EvtRcdClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.
LPHD1.RsStat.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.
OscRDRE1.RcdTrg.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command FORCE TRIGGER.
OscRDRE1.MemClr.ctlModel
Range: direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the command CLEAR OSCILLOGRAPHY.