CHAPTER 5: SETTINGS FLEXLOGIC
B90 LOW IMPEDANCE BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL 5-143
5
ELEMENT:
Instantaneous
overcurrent
IOC 1 PKP
IOC 1 DPO
IOC 1 OP
Instantaneous overcurrent 1 element has picked up
Instantaneous overcurrent 1 element has dropped out
Instantaneous overcurrent 1 element has operated
IOC 2 to 24 Same set of operands as shown for IOC 1
ELEMENT:
Isolator monitoring
ISOLATOR 1 POSITION
ISOLATOR 1 ALARM
ISOLATOR 1 BLOCK
Position of isolator 1 (ON = closed; OFF = open)
Contact discrepancy detected for isolator 1
Blocking signal for substation switching operations set due to contact
discrepancy of isolator 1 (acknowledgeable)
ISOLATOR 2 to 48 Same set of operands as shown for ISOLATOR 1
ELEMENT:
Non-volatile latches
LATCH 1 ON
LATCH 1 OFF
Non-volatile latch 1 is ON (Logic = 1)
Non-volatile latch 1 is OFF (Logic = 0)
LATCH 2 to 16 Same set of operands as shown for LATCH 1
ELEMENT:
Setting group
SETTING GROUP ACT 1
SETTING GROUP ACT 2
SETTING GROUP ACT 3
SETTING GROUP ACT 4
SETTING GROUP ACT 5
SETTING GROUP ACT 6
Setting group 1 is active
Setting group 2 is active
Setting group 3 is active
Setting group 4 is active
Setting group 5 is active
Setting group 6 is active
ELEMENT:
Time overcurrent
TOC 1 PKP
TOC 1 DPO
TOC 1 OP
The time overcurrent 1 element has picked up
The time overcurrent 1 element has dropped out
The time overcurrent 1 element has operated
TOC 2 to 24 Same set of operands as shown for TOC 1
ELEMENT:
Trip bus
TRIP BUS 1 PKP
TRIP BUS 1 OP
Asserted when the trip bus 1 element picks up
Asserted when the trip bus 1 element operates
TRIP BUS 2 to 6 Same set of operands as shown for TRIP BUS 1
ELEMENT:
Undervoltage
UNDERVOLTAGE 1 PKP
UNDERVOLTAGE 1 DPO
UNDERVOLTAGE 1 OP
The undervoltage 1 element has picked up
The undervoltage 1 element has dropped out
The undervoltage 1 element has operated
UNDERVOLTAGE 2 to 12 Same set of operands as shown for UNDERVOLTAGE 1
FIXED OPERANDS Off Logic = 0. Does nothing and can be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS:
Contact inputs
Cont Ip 1 On
Cont Ip 2 On
Cont Ip 1 Off
Cont Ip 2 Off
Cont Ip 120 On
Cont Ip 120 Off
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
current
(from detector on
form-A output only)
Cont Op 1 IOn
Cont Op 2 IOn
Cont Op 72 IOn
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
Cont Op 1 VOn
Cont Op 2 VOn
Cont Op 72 VOn
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
Cont Op 1 VOff
Cont Op 2 VOff
Cont Op 72 VOff
(does not appear unless ordered)
(does not appear unless ordered)
(does not appear unless ordered)
INPUTS/OUTPUTS:
Direct inputs
DIRECT INPUT 1 On
DIRECT INPUT 256 On
Flag is set, logic=1
Flag is set, logic=1
Operand type Operand syntax Operand description