DATA EXCHANGE
D485 MODBUS TO DEVICENET CONVERTER – USER GUIDE 3–9
Table 3–13: Attributes for instance 2 for connection object 05h
Attr. Access Name Type Value Description
1 Get State USINT N/A 0 = Non existent
1 = Configuring
3 = Established
4 = Timeout
2 Get Instance type USINT 0 I/O connection
Table 3–14: Attributes for instance 3 for connection object 05h
Attr. Access Name Type Value Description
1 Get State USINT N/A 0 = Non existent
1 = Configuring
3 = Established
4 = Timeout
2 Get Instance type USINT 0 I/O connection
Table 3–15: Attributes for instance 4 for connection object 05h
Attr. Access Name Type Value Description
1 Get State USINT N/A 0 = Non existent
1 = Configuring
3 = Established
4 = Timeout
2 Get Instance type USINT 0 I/O connection
3 Get Transport class
trigger
BYTE N/A Defines the behavior of the
connection
4 Get Produced
connection ID
UINT N/A CAN ID for transmission
5GetConsumed
connection ID
UINT N/A CAN ID for reception
6 Get Initial
communication
characteristics
BYTE 0Fh (no ACK) Produces over message group 1.
Does not consume.
01h (ACK) Produces over message group 1.
Consumes over message group
2.
7 Get Produced
connection size
UINT N/A Number of bytes transmitted
across this connection
8GetConsumed
connection size
UINT 0 Number of bytes received across
this connection
9 Get/Set Expected packet
rate
UINT 0 Timing associated with this
connection
12 Get Watchdog
timeout action
USINT N/A 0 = Transition to the timed
out state
1 = Auto delete
2 = Auto reset
3 = Deferred delete
13 Get Produced
connection path
length
UINT 0006h Number of bytes in the produced
connection path attribute
14 Get Produced
connection path
EPATH 20 04 24 66
30 03h
Application object producing
data on this connection
15 Get Consumed
connection path
length
UINT 0004h Number of bytes in the
consumed connection path
length attribute
16 Get Consumed
connection path
EPATH 20 2B 24
01h
Specifies the application object(s)
that are to receive the data
consumed by this connection
object