DigitalFlow™ GF868 Programming Manual (1-Channel) 119
Appendix E. Foundation Fieldbus Tables
Appendix E. Foundation Fieldbus Tables
Table 23: GE Fieldbus Device Capability, XGX868 Family of Meter Types 
Model
GF868, GS868, GM868, XGF868i, XGM868i, and 
XGS868i
1 --General
1.1 Is the Device registered at the Fieldbus Foundation 
(Yes/No)
Yes
1.2 Is the Unit released to production, and if not, when? Yes
1.3 Is there any special functionality that device supports 
(e.g., display blocks, diagnostic blocks)?
No
1.4 Manufacturer Name GE Measurement & Control
1.5 Model GE Measurement & Control Gas Flowmeter
1.6 Device Type 0002
1.7 FF Device Revision 02
1.8 Does the device require special programming 
software to configure a ‘good’ status on the PV?
Yes
1.9 Does the Device feature a Non-Volatile Memory 
protection feature? If so, what are the steps to 
disable/enable from the Resource or Transducer 
block.
No
1.10 HOST System registered Yokogawa (TBD), Emerson, Honeywell (TBD), 
ABB (TBD)
1.11 Design Concept Entity Concept
1.12 FISCO Compliant? No
1.13 FNICO Compliant? Yes: models XGM868i, XGS868i, XGF868i; No: 
others
1.14 Hazardous Location Certs GF868, GM868, GS868: CSA for non-incendive 
Div 2, Class 1, Gr A, B, C, & D. IP66
Optional: Div 1, Class 1, Gr C & D or
ATEX II 2 G Ex d IIC T6 IP66 or
IECEx II2 G Ex d IIC T6 Gb IP66
XGM868i, XGS868i, XGF868i: CSA Div 1, Class 1, 
Gr B, C, & D and ATEX II 2 G D Ex d IIC T5 IP66 
and
IECEx II 2 G Ex d IIC T6 Gb IP66
1.15 FF Liquid PCB p/n:                    XMT868i / DF868 
1.16 FF Gas PCB p/n:                        XGx868i / Gx868  703-1475-04 (rev J)/ 703-1491-04