5-24 F650 Digital Bay Controller GEK-113000AE
5.2 FIRMWARE UPGRADE VERSION V7.00 OR HIGHER 5 BOOTCODE AND FIRMWARE UPGRADE
5
3. Enter communication parameters of the relay that is going to be upgraded and click on "Upgrade" button
Figure 5–37: RELAY COMMUNICATION PARAMETERS
If the IP address is not the correct one, then the following message will appear:
Figure 5–38: UNABLE TO CONNECT TO IP
4. If the IP address is correctly set, then the message "*.SFD Sending file" will be displayed in the main screen. Sending
file status bar will show the progress.
Figure 5–39: UPGRADE INITIALIZATION