Chapter 5. Diagnostics
120 PACSystems* RX3i & RSTi-EP PROFINET IO-Controller User Manual GFK-2571N
Group/
Category/
Type/
Descriptor
Description
Cause
Recommended
Correction
7-34-0-0
Addition of
network interface.
A configured PROFINET
interface that was
previously reported lost has
been added to the device.
None.
7-36-0-0
Addition of
network port.
A configured PROFINET
port that was previously
reported lost has been
added to the device.
None.
7-36-1-0
Network port
released by
PROFINET IO
Supervisor.
A configured PROFINET
port that was previously
controlled by a PROFINET
IO Supervisor has been
released.
None.
9-6-10-0
Multiple Media
Redundancy
Managers have
been detected on
the network.
The PROFINET Controller is
configured as a Media
Redundancy Manager and
other Media Redundancy
Managers are currently
present on the network.
Update the PROFINET Controller
configuration to change its MRP role
to either Disabled or Client, or remove
all of the other devices on the
network that are also acting as a
Media Redundancy Manager.
9-6-11-0
Multiple Media
Redundancy
Managers are no
longer present on
the network.
The PROFINET Controller is
configured as a Media
Redundancy Manager and it
had detected that multiple
Media Redundancy
Managers were on the
network, but now those
other managers are no
longer present.
No action necessary. The network is
expected to only have a single Media
Redundancy Manager present.
9-6-12-0
The Media
Redundancy
Manager has
detected that the
network ring has
been broken.
The PROFINET MRP
network ring is broken.
The MRP Ethernet ring is broken.
Possible causes include damaged or
disconnected cable or power loss to a
node or switch. Locate and repair the
cause(s).
9-6-13-0
The Media
Redundancy
Manager has
detected that the
network ring has
been repaired.
The PROFINET MRP
network ring is closed/okay.
No action necessary. This is the
normal, expected state of an MRP
Ethernet ring.
9-11-3-1
Invalid MAC
address detected.
PROFINET Controller no
longer has a valid MAC
address.
Contact customer service.
9-11-3-3
Media redundancy
configuration error.
The PROFINET Controller
has encountered a problem
attempting to configure
media redundancy
operation.
Contact customer service.