Chapter 5. Diagnostics
GFK-2571N May 2018 121
Group/
Category/
Type/
Descriptor
Description
Cause
Recommended
Correction
9-11-3-4
All critical network
ports are
disconnected.
The PROFINET Controller
has detected that all the
configured critical network
ports have lost their links
and are no longer
connected.
Reconnect the configured critical
network ports.
9-11-5-z
13
Internal runtime
error.
PROFINET Controller has
encountered an internal
error during its operation.
Contact customer service.
9-18-1-1
PNC001 module
exceeded its
recommended
operating
temperature.
The temperature detected
by the PNC001 module has
exceeded its safe operating
temperature.
Reduce the temperature of the
environment where the PNC001
module is operating.
9-18-1-2
Watchdog Timeout
Error
PNC001 application code
restarted due to a
hardware watchdog
timeout.
Contact customer service.
9-69-0-0
PROFINET
Controller has
become heavily
loaded.
The PROFINET Controller
has become heavily loaded
with activity.
PROFINET Controller is
running at or above the
maximum supported load.
I/O updates experienced by
the PLC may be slower than
optimal. Refer to Section
3.1.1.
No action is required if no PROFINET
system performance is observed. If
action is required to run the
PROFINET Controller at or below the
maximum supported load, reduce the
load on PROFINET Controller, using
one or both of the following methods:
Increase the configured update
rate value (i.e. IO received less
frequently) of one or more
PROFINET Devices configured on
the PROFINET Controller.
Reduce the number of PROFINET
Devices configured on the
PROFINET Controller.
9-70-0-0
PROFINET
Controller is no
longer heavily
loaded.
Load applied to PROFINET
Controller has been
reduced to or below the
maximum supported load,
after it was previously
heavily loaded. Refer to
Section 3.1.1.
None.
13
z: Runtime error detail. Inform value of z to customer support.