ADP200 • Quick installation guide - Specifications and connection 13
4.4 Input electrical data
Connection to TT and TN networks ���������� yes
Choke ������������������������������� Sizes 2...3: Optional (AC side), sizes 4-5 : integrated (DC side)
Size Input
voltage
Uln
Input
frequency
THD % Overvoltage
threshold
(Vdc)
Undervoltage
threshold
(Vdc)
In AC input current for continuous operation DC-Link
Capacity
@ 230 Vac
(Arms)
@ 400 Vac
(Arms)
@ 480 Vac
(Arms)
(Vac) (Hz) @230V @400V @480V Without
input
choke
With
input
choke
Without
input
choke
With
input
choke
Without
input
choke
With
input
choke
(µF)
2075
three-phase
230-400-
480Vac
-15%+10%
50/60 Hz,
± 5%
< 75
(1)
< 40
(2)
< 75
(1)
< 50
(2)
< 70
(1)
< 60
(2)
820 Vdc
@ 480 Vac = 470 Vdc
@ 460 Vac = 450 Vdc
@ 400 Vac = 391 Vdc
@ 230 Vac = 225 Vdc
24 20 24 20 21 19 680
2110
< 75
(1)
< 40
(2)
28 24 28 25 25 24 1020
3150
< 75
(1)
< 40
(2)
40 34 40 35 35 33 1500
3185
< 75
(1)
< 40
(2)
48 42 48 44 43 41 2250
3220
< 75
(1)
< 40
(2)
51 45 51 47 46 44 2700
4300
(3)
< 40
(1)
< 45
(1)
< 55
(1)
64 - 65 - 61 - 2350
4370
(3)
< 40
(1)
79 - 80 - 75 - 2350
4450
(3)
< 40
(1)
96 - 99 - 93 - 2800
5550
(3)
< 40
(1)
112 - 116 - 109 - 4700
5750
(3)
< 40
(1)
158 - 161 - 148 - 5600
5S550
(4)
< 40
(1)
< 55
(1)
< 65
(1)
-
113 - 120 - 114 4700
5S750
(4)
< 40
(1)
< 45
(1)
< 55
(1)
-
158
-
161
-
148
5600
(1) @ rated Iout without AC input chokes.
(2) with LR3 AC input chokes.
(3) with integrated DC input choke, in accordance with EN 61800-3.
(4) ADP200-5S550 and 5S750 models: AC input external choke is mandatory.
4.5 Output electrical data
Motor type ��������������������������� Synchronous
Maximum output voltage U2 �������������� 0.98 x Uln (Uln = AC input voltage)
Maximum output frequency f2 ������������� 300 Hz
Size In
Rated output current
(fsw = default)
Pn mot
(Recommended motor power,
fsw = default)
fsw (4)
Switching
frequency
Reduction
factor
IGBT
braking unit
@Uln =
230Vac
@Uln =
400Vac
@Uln =
460Vac
@Uln =
230Vac
@Uln =
230Vac
@Uln =
400Vac
@Uln =
460Vac
Other Default Kt Kalt Kv
(A) (A) (A)
(kW) (Hp) (kW) (Hp) (kHz) (kHz)
(1) (2) (3)
2075 18.5 18.5 16.7 4 5 7.5 10 8 4 0.9 1.2 0.9
Standard internal (with
external resistor);
braking torque 150%
MAX
External optional on
5750 size.
2110 22 22 19.8 5.5 7.5 11 15 8 4 0.9 1.2 0.9
3150 32 32 28.8 7.5 10 15 20 8 4 0.9 1.2 0.9
3185 39 39 35.1 9 15 18.5 25 8 4 0.9 1.2 0.9
3220 42 42 37.8 11 15 22 30 8 4 0.9 1.2 0.9
4300 60 60 54 15 20 30 40 8 4 0.9 1.2 0.9
4370 75 75 67.5 18.5 25 37 50 8 4 0.9 1.2 0.9
4450 90 90 81 22.0 30 45 60 8 4 0.9 1.2 0.9
5550 / 5S550 105 105 94 30 40 55 75 8 4 0.9 1.2 0.9
5750 - 5S750 150 150 135 37 50 75 100 8 4 0.9 1.2 0.9
The derating factors shown in the table are applied to the rated DC output by the user. They are not automatically
implemented by the drive: Idrive = In x Kalt x Kt x Kv
(1) Kt: Derating factor for ambient temperature of 50°C (1% every °C above 40°C)
(2) Kalt: Derating factor for installation at altitudes above 1000 meters a.s.l. Value to be applied = 1.2% each 100 m increase above 1000 m (up to a maximum of 2000 m).
E.g.: Altitude 2000 m, Kalt = 1.2% * 10 = 12% derating; In derated = (100 - 12) % = 88 % In
(3) Kv : Derating factor for mains voltage at 460/480Vac.
(4) There is also the possibility to set a variable switching frequency through parameter setting.