ADP200 • Quick installation guide - Specifications and connection 21
5.2.2 DC input chokes
Size THD (%)
In
(@400V/50Hz, with DC
input chokes)
(A)
Model Code
Dimensions: WxHxd
mm [inches]
Weight
kg [lbs]
2075
< 35 %
16
LDC-007 S7AI12 125 x 122 x 127 [4.92 x 4.8x5] 4.9 [10.8]
2110
21
LDC-011 S7AI13 125 x 142 x 127 [4.92 x 5.59 x 5] 6.6 [14.55]
3150
28
LDC-015 S7AI14 125 x 152 x1 27 [4.92 x 5.98 x 5] 8 [17.63]
3185 35 LDC-022 S7AI15 155 x 148 x 160 [4.92 x 5.82 x 6.3] 8.5 [18.74]
3220
40
LDC-022 S7AI15 155 x 148 x 160 [4.92 x 5.82 x 6.3] 8.5 [18.74]
4300
45
Internal choke
4370
40
4450
45
5550
50
5750
40
Note! The DC input choke is not integrated and can not be connected on ADP200-5S550 / ADP200-5S750 sizes.
5.3 AC output chokes
The ADP200 inverter can be used with standard motors or motors designed specically for use with inverters.
The latter usually have a higher isolation rating to better withstand PWM voltage. Examples of reference regulations
are provided below: motors designed for use with inverters do not require any specic ltering of output from the
inverter. For standard motors, especially with long cable runs (typically over 100 m) an output choke may be necessary
to maintain the voltage waveform with the specied limits.
The range of recommended chokes are listed in the following table. The rated current of the chokes should be approx.
20% higher than that of the inverter in order to take into account additional losses due to modulation of the output
waveform.
Size Model Code
Dimensions: WxHxd
mm [inches]
Weight
kg [lbs]
2075 LU3-011 S7FG4 180 x 185 x130 8 [17.64]
2110 LU3-011 S7FG4 180 x 185 x130 8 [17.64]
3150 LU3-015 S7FH2 180 x 185 x140 7 [15.43]
3185 LU3-022 S7FH3 180 x 185 x160 8.2 [18.08]
3220 LU3-022 S7FH3 180 x 185 x160 8.2 [18.08]
4300 LU3-030 S7FH4 180 x 185 x170 10 [22.05]
4370 LU3-037 S7FH5 180 x 185 x170 10 [22.05]
4450 LU3-055 S7FH6 240 x 216 x170 16 [35.27]
5550 / 5S550 LU3-055 S7FH6 240 x 216 x170 16 [35.27]
5750 / 5S750 LU3-090 S7FH10 180 x 165 x195 15 [33.07]
Note! With the inverter operated at the rated current and a frequency of 50 Hz, the output chokes cause a voltage drop of approx. 2% of the output voltage.