ADP200 • Quick installation guide - Specifications and connection 33
7.1.7 Connection of AC and DC chokes
Size AC-Choke DC-Choke
2075
Optional (*)
(*) Mandatory if Pcc line exceeds the values on chapter "5.2.1 AC
input chokes".
Optional
2110
3150
3185
3220
4300
Optional Integrated
4370
4450
5550
5750
5S550
Mandatory Not integrated and not connectable (no terminals)
5S750
The drive can use both a three-phase choke on the AC power line and, for 7.5 to 22 kW drives only, a DC choke be-
tween terminals C1 and C.
Refer to chapter 5.2 for the recommended chokes.
If no DC choke is used, terminals C1 and C must be bridged (sizes 2 and 3).
7.1.7.1 Connection of AC choke
ADP200-2075...3220 ADP200-4300...5550
L1 L2 L3 BR C1 CDUVW
K1M
L1 L2 L3
F1
( 400- 50/60 Hz)3ph, 230- 480 VAC
,
AC chokes
(optional)
L1 L2 L3 BR1 CDUVWBR2
K1M
L1 L2 L3
F1
( 400- 50/60 Hz)3ph, 230- 480 V
AC
,
AC chokes
(optional)
ADP200-5750 ADP200-5S550 - ADP200-5S750
L1 L2 L3 CDUVW
K1M
L1 L2 L3
F1
( 400- 50/60 Hz)3ph, 230- 480 V
AC,
AC chokes
(optional)
K1M
L1 L2 L3
F1
(3ph, 230-400-480 V
AC, 50/60 Hz)
AC chokes
(optional)
7.1.7.2 Connection of DC choke
ADP200-2075...3220
L1 L2 L3 BR C1 CDUVW
K1M
L1 L2 L3
F1
( 400- 50/60 Hz)3ph, 230- 480 V
AC
,
DC choke
(optional)
Attention