42 ADP200 • Quick installation guide - Specifications and connection
A) Connection of an industrial PC with RS485
The following are required for connection:
• shielded cable for the RS485 / RS485 connection (see gure 7.5.2), code 8S864C.
B) Connection to a PC with RS232 port and OPT-RS485-ADP option (isolated, for point to point and multidrop)
The following are required for connection:
• optional OPT-RS485-ADP card (for galvanic isolation), code S5L85
• an optional PCI-COM adapter, code S560T
• a shielded cable (code 8S864C) for connection to the RS485 port of the drive to the RS232 connector of the PC,
see gure 7.5.2.
C) Connection to a PC with RS232 port (not isolated)
The following are required for connection:
• an optional PCI-COM adapter, code S560T
• a shielded cable (code 8S864C) for connection to the RS485 port of the drive to the RS232 connector of the PC,
see gure 7.5.2.
D) Connection to a PC with USB port (not isolated)
The following are required for connection:
• an optional USB/RS232 adapter, code 8S8F62 (including the cable for USB connection)
• an optional PCI-COM adapter, code S560T
• a shielded cable (code 8S864C) for connection to the RS485 port of the drive to the USB/RS232 adapter, see
gure 7.5.2.
7.4.2 Drive / RS485 port point-to-point connection (isolated)
To make the connection with galvanic isolation, the OPT-RS485-ADP optional card is required.
The card is equipped with a 9-pin D-SUB male receptacle connector which must be inserted in the RS485 connector of
the ADP200 drive.
Connect P1 side to RS485 connector of ADP200, and J1 side to the PC serial line, the adapters indicated in paragraph
7.4.1 must be used.
OPT-RS485-ADP (cod. S5L85) J1 Pin Description S1
9-pin D-SUB Female,
to serial cable
P1
J1
ON OFF
9-pin D-SUB Male,
ADP side
1 N.C.
To insert termination switch
set S1-1/2 to ON
2 N.C.
3 A
4 EQP
5 Reserved
6 Reserved
7 B
8 N.C.
9 N.C.
Figure 7.5.3: OPT-RS485-ADP card
7.4.3 RS 485 multi-drop connection
For the multi-drop connection, the OPT-RS485-ADP optional card must be installed on each drive; the ends of the con-
nection must have S1 termination switch set to ON. The multi-drop connection is always galvanically insulated.
Up to 20 drives can be connected; the maximum length of the connection is 200 meters.
ADP200 ADP200 ADP200
OPT-RS485-ADP
3
7
4
EQP
B
A
S1=ON S1=OFF S1=ON
OPT-RS485-ADP OPT-RS485-ADP
Industrial PC,
PLC,
etc..
(with RS485)
ADP200 ADP200 ADP200
RS485 444
EQP
B
A
S1=OFF S1=OFF S1=ON
OPT-RS485-ADP OPT-RS485-ADP OPT-RS485-ADP
Termination=ON
Industrial PC,
PLC,
etc..
(with RS485)
Termination=OFF
RS485