20 ADP200 • Quick installation guide - Specifications and connection
5.2 Input chokes
The three-phase mains choke is strongly recommended in order to:
- limit the RMS input current of the ADP200 inverter,
- increase the life of intermediate circuit capacitors and reliability of input diodes,
- reduce mains harmonic content,
- reduce problems due to power supply via a low impedance line (≤ 1.3%).
5.2.1 AC input chokes
AC mains 230V/50Hz,
Size
Pmotor
recommended
In
(without AC input
chokes)
(A)
In
with LR3 AC input chokes
Pcc mains max,
without AC input
chokes
(kVA)
Input THD
@ rated Iout
without AC input
chokes
Input THD
@ rated Iout
with LR3 AC input
chokes
(A) mH, model (code)
2075
4 24
20 0.89mH, LR3y-2075 (S7AB6) 461 <75 <40
2110
5.5 28
24 0.68mH, LR3y-3110 (S7AB7) 548 <75 <40
3150
7.5 40
34 0.51mH, LR3y-3150 (S7AB8) 797 <75 <40
3185
9 48
42 0.35mH, LR3-22 (S7FF4) 971 <75 <40
3220
11 51
45 0.35mH, LR3-22 (S7FF4) 1,046 <75 <40
4300
15 64 - - - <40 -
4370
18.5 79 - - - <40 -
4450
22.0 96 - - - <40 -
5550
30 112 - - - <40 -
5750
37 158 - - - <40 -
5S550
30 - 113 0.13mH, LR3-055 (S7FF1) - (*) <40
5S750
37 - 158 0.15mH, LR3-090 (S7D19) - (*) <40
AC mains 400V/50Hz,
Size
Pmotor
recommended
In
(without AC input
chokes)
(A)
In
with LR3 AC input chokes (code)
Pcc mains max,
without AC input
chokes
(kVA)
Input THD
@ rated Iout
without AC input
chokes
Input THD
@ rated Iout
with LR3 AC input
chokes
(A) mH, model (code)
2075
7.5 24
20 0.89mH, LR3y-2075 (S7AB6) 986 <75 <50
2110
11 28
25 0.68mH, LR3y-3110 (S7AB7) 1,172 <75 <50
3150
15 40
35 0.51mH, LR3y-3150 (S7AB8) 1,705 <75 <50
3185
18.5 48
44 0.35mH, LR3-22 (S7FF4) 2,078 <75 <50
3220
22 51
47 0.35mH, LR3-22 (S7FF4) 2,238 <75 <50
4300
30 65 - - - <45 -
4370
37 80 - - - <45 -
4450
45 99 - - - <45 -
5550
55 116 - - - <45 -
5750
75 161 - - - <45 -
5S550
55 - 120 0.13mH, LR3-055 (S7FF1) - (*) <55
5S750
75 - 161 0.15mH, LR3-090 (S7D19) - (*) <45
AC mains 480V/50Hz,
Size
Pmotor
recommended
In
(without AC input
chokes)
(A)
In
with LR3 AC input chokes (code)
Pcc mains max,
without AC input
chokes
(kVA)
Input THD
@ rated Iout
without AC input
chokes
Input THD
@ rated Iout
with LR3 AC input
chokes
(A) mH, model (code)
2075
7.5 21
19 0.89mH, LR3y-2075 (S7AB6) 1,065 <70 <60
2110
11 25
24 0.68mH, LR3y-3110 (S7AB7) 1,266 <70 <60
3150
15 35
33 0.51mH, LR3y-3150 (S7AB8) 1,842 <70 <60
3185
18.5 43
41 0.35mH, LR3-22 (S7FF4) 2,245 <70 <60
3220
22 46
44 0.35mH, LR3-22 (S7FF4) 2,417 <70 <60
4300
30 61 - - - <55 -
4370
37 75 - - - <55 -
4450
45 93 - - - <55 -
5550
55 109 - - - <55 -
5750
75 148 - - - <55 -
5S550
55 - 114 0.13mH, LR3-055 (S7FF1) - (*) <65
5S750
75 - 148 0.15mH, LR3-090 (S7D19) - (*) <55
Note:
- For the standard application of the ADP200 (injection molding machine with servopump), LR3 input choke for sizes 7.5kW to 22kW can be omitted only if the Pcc
line is below the values shown in the table.
- For other applications, the input choke may be mandatory. Please contact Gefran’s sales department for further information and details.
(*) AC input choke is mandatory on ADP200-5S550 / ADP200-5S750 sizes.
- Use of the input choke extends the life of the drive