ADP200 • Quick installation guide - Specifications and connection 47
8.1.2 KB-ADV100 optional programming keypad
Drive status indicator LEDs
T+ T- EN ILim n=0 AL
E
DISPESC
FWD
REV
CUST
LOC
REM
RST
01 MONITOR
02 DRIVE INFO
03 STARTUP WIZARD
04 DRIVE CONFIG
05 REFERENCES
5-line x 21 character alphanumerical LCD display
Membrane keypad
The optional programming keypad is used to display the status and diagnostics parameters during operation. It has
a strip of magnetic material on the back so that it can be attached to the front of the drive or other metal surface (e.g.
door of the electrical panel). The keypad can be used remotely from distances of up to 15 m. A 70 cm-long connec-
tion cable is supplied as standard. Up to 5 sets of parameters can be saved using the KB-ADV100 keypad and sent to
other drives.
8.1.2.1 Membrane keypad
This section describes the keys on the membrane keypad and their functions
Symbol Reference Description
Start Starts the motor
Stop Stops the motor
ESC Escape
Returns to the higher level menu or submenu. Exits a parameter, a list of parameters, the list of the last 10 parameters.
Can be used to exit a message that requires use of this.
FWD
REV
Forward/Reverse Reverses the direction of rotation of the motor
LOC
REM
Local/Remote
Changes the method of use from local to remote and vice versa.
Is active only if the drive is not enabled.
RST Reset Resets alarms, only if the causes have been eliminated.
CUST Custom
Displays the last 10 parameters that have been modified. To exit these functions, press the key.
DISP Display Displays a list of drive functioning parameters.
E Enter
Enters the submenu or selected parameter, or selects an operation. It is used when modifying parameters to confirm the new
value that has been set.
Up
Moves the selection up in a menu or list of parameters.
During modification of a parameter, increases the value of the digit under the cursor.
Down
Moves the selection down in a menu or list of parameters.
During modification of a parameter, decreases the value of the digit under the cursor.
Left Returns to the higher level menu. During modification of a parameter, moves the cursor to the left.
Right Accesses the submenu or parameter selected. During modification of a parameter, moves the cursor to the right.
8.1.2.2 Meaning of LEDs
LEDs Colour Meaning of LEDs
T+ Yellow the LED is lit, when the drive operates with a positive torque
T- Yellow the LED is lit, when the drive operates with a negative torque
EN Green The LED is lit during IGBT modulation (drive operating)
ILIM Red When this LED is lit the drive has reached a current limit condition. During normal functioning, this LED is off.
N=0 Yellow The LED is lit when motor speed is 0.
AL Red The LED is lit when the drive signals that an alarm has been triggered

Table of Contents