ADP200 • Quick installation guide - Specifications and connection 19
5- Options
5.1 Optional external fuses
5.1.1 Network side fuses (F1)
The inverter must be fused upstream on the network side.
Use fast-acting fuses only.
Size
F1 - External network side fuses
DC link capacitor hours of
service life [h]
EUROPE AMERICA
Without mains
choke (*)
With mains
choke
Type Code Type Code
2075 > 20000 > 50000 GRD3/35 F4D20 A70P40 S7G52
2110 > 20000 > 50000 Z22GR40 F4M16 A70P40 S7G52
3150 > 20000 > 50000 Z22GR63 F4M17 A70P60-4 S7I34
3185 > 20000 > 50000 Z22GR80 F4M19 A70P80 S7G54
3220 > 20000 > 50000 Z22GR80 F4M19 A70P80 S7G54
4300 > 25000 - Z22GR80 F4M19 A70P80 S7G54
4370 > 25000 - Z22GR100 F4M21 A70P100 S849B
4450 > 25000 - Z22GR100 F4M21 A70P100 S849B
5550 > 25000 - S00/üf1/80/200A/690V F4G23 A70P200 S7G58
5750 > 25000 - S00/üf1/80/200A/690V F4G23 A70P200 S7G58
5S550 > 25000 50000 S00/üf1/80/200A/690V F4G23 A70P200 S7G58
5S750 > 25000 50000 S00/üf1/80/200A/690V F4G23 A70P200 S7G58
Technical data for fuses, including dimensions, weights, power leakage, fuse carriers etc. are reported in the corresponding manufacturers' data sheets:
GRD... (E27), S00... Jean Müller, Eltville
A70... Ferraz
(*) Pcc max