80 ADP200 • Quick installation guide - Specifications and connection
10.3 Messages
Note ! For more information see chapter 8.7.
Index Error message shown on
the display [on the inte-
grated keypad]
Sub-code Description
1 Load default param [LDEF]
Condition: may occur during loading of the parameter database saved in flash normally appears in the following conditions: at initial power-on when a
new firmware version is downloaded, when the regulation is installed on a new size, when the region is changed.
If this message is displayed when the drive is already operating, this means that a problem has occurred in the parameter database saved in Flash.
If this message is displayed, the drive automatically performs the Load default command.
0001H-1 The database saved is not valid
0002H-2 The database saved is not compatible
0003H-3 The database saved refers to a different size from the current size
0004H-4 The database saved refers to a different region from the current region
Solution: Set the parameters to the value required and perform Save parameter
2
3
4
Option detect slot 1 [OPT1]
Option detect slot 2 [OPT2]
Option detect slot 3 [OPT3]
Condition: when the drive is turned on it recognises the presence of an optional card. One of the messages is shown on the display for a few seconds
0H-0 None
0004H-4 CAN
0008H-8 Enc 1 (EXP-DE-I1R1F2-ADL)
0108H-264 Enc 2 (EXP-SE-I1R1F2-ADL)
0208H-520 Enc 3 (EXP-SESC- I1R1F2-ADL)
0308H-776 Enc 4 (EXP-EN/SSI- I1R1F2-ADL)
0408H-1032 Enc 5 (EXP-HIP- I1R1F2-ADL)
0508H-1288 Enc 6 (EXP-RES-I1-ADP/ EXP-RES-I1R1-ADP)
0101H-257 I/O 1 (EXP-IO-D4-ADL)
0501H-1281 I/O 2 (EXP-IO-D8R4-ADL)
0901H-2305 I/O 3 (EXP-IO-D16R4-ADL)
0F01H-3841 I/O 4 (EXP-IO-D12A2R4-ADL)
1301H-4865 I/O 5 (EXP-IO-D8A4R4-ADL)
1501H-5377 I/O 6 (EXP-IO-D5R3-F-ADL)
1F01H-7937 I/O 7 (EXP-IO-D10A3R2-ADP)
2301H-8961 I/O 8 (EXP-IO-D8A4R2-ADP)
00FFH-255 Unknown
Solution:
5 Autotune (motor) Condition: this may occur during the Autotune procedure
[SLFT] 0 No error
1
The commands are not configured in Local mode.
Solution: Execute the requested configuration
2
The Commands local sel parameter has not been configured from the keypad
Solution: Execute the requested configuration
3
The motor plate data parameters have changed but the Take parameters command, PAR 2020, has not been executed
Solution: Execute the Take parameters command.
4
The motor is not connected
Solution: Connect the motor
5
While running self-tuning the ESC key was pressed or the enable contact was opened or an alarm occurred. The Autotune command
was sent with the drive in the alarm condition
Solution: Eliminate the reason for the alarm, remove the reason for the opening of the enable contact, reset alarms.
6
A setting performed by the Autotune function produced a parameter value outside the min or max range.
Solution: Check the motor plate data or drive and motor sizes have been combined incorrectly.
7
The Autotune command was sent without being enabled.
Solution: Close the enable contact before sending the Autotune command
8
Internal calculation error concerning IGBT control
Solution: Perform autotuning once more, if the problem persists, contact the Gefran technical support centre.
9
The drive has measured a stator resistance value exceeding the set limit.
Solution: contact the Gefran technical support centre.
10
The drive has measured a stator resistance value below the set limit.
Solution: contact the Gefran technical support centre.
11-12
Measurement of DTL internal compensation voltage outside accepted range.
Solution: check connection between drive and motor.
If correct, the drive is faulty, contact the Gefran technical support centre.