ADP200 Application PID-IMM User Manual Pag. 48 of 80
11562 = DivSpeedRef: source of Speed Ref is external CANopen master
(Divergent mode)
This two parameters are used only in case of multi-pump Convergent/divergent in
divergent mode only and the Divergent Master drive
[11002] MasterSlave = SlaveDivMaster.
Pressure Ref source Selection of source for pressure reference signal.
Assigned from:
0 = Digital Param: source is local parameter.
1500 = Analog Input S: source is analog input port S = sensor (T2:70-71-72)
1600 = Analog Input 1: source is analog input 1 (T2:42-43)
1650 = Analog Input 2: source is analog input 2 (T2: 40-41)
3700 = Pad 1 source is system pad1 (see menu FUNCTIONS / PADS).
3702 = Pad 2 source is system pad2
…….
…….
3730 = PAD16: source is system pad16 (see menu FUNCTIONS / PADS).
4024 = Fieldbus M->S1 source is fieldbus process data channel 1.
4034 = Fieldbus M->S2 source is fieldbus process data channel 2
…….
…….
4094 = Fieldbus M->S8: source is fieldbus process data channel 8
11554 = PLCPressRef: source of Press. Ref. is external CANopen master
(Convergent mode)
11556 = PLCSpeedRef: source of Speed Ref. is external CANopen master
(Convergent mode)
This two parameters are used only in case of multi-pump Master Drive with PID
IMM/CAN/[11626]CANMPacrive = ON
11560 = DivPressRef: source of Press. Ref. is external CANopen master
(Divergent mode)
11562 = DivSpeedRef: source of Speed Ref is external CANopen master
(Divergent mode)
This two parameters are used only in case of multi-pump Convergent/divergent in
divergent mode only and the Divergent Master drive
[11002] MasterSlave = SlaveDivMaster.
Flow Ref Source Selection of source for flow reference signal (speed reference).
Assigned from:
0 = Digital Param: source is local parameter.
1500 = Analog Input S: source is analog input port S = sensor (T2:70-71-72)
1600 = Analog Input 1: source is analog input 1 (T2:42-43)
1650 = Analog Input 2: source is analog input 2 (T2: 40-41)
3700 = Pad 1 source is system pad1 (see menu FUNCTIONS / PADS).
3702 = Pad 2 source is system pad2
…….
…….
3730 = PAD16: source is system pad16 (see menu FUNCTIONS / PADS).
4024 = Fieldbus M->S1 source is fieldbus process data channel 1.
4034 = Fieldbus M->S2 source is fieldbus process data channel 2
…….
…….
4094 = Fieldbus M->S8: source is fieldbus process data channel 8
11554 = PLCPressRef: source of Press. Ref. is external CANopen master
(Convergent mode)
11556 = PLCSpeedRef: source of Speed Ref. is external CANopen master
(Convergent mode)

Other manuals for gefran ADP200