Section 2 — Operation
E Option Control Panels
E PANEL MASTER CONTROL BOX CONFIGURATION SETTINGS
ENGINE PARAMETER MENU
Parameter Value Units
RS232 Port
or RS485 Port
Restore All Values to
Default Settings
Voltage Scaling Factor
Flywheel Teeth Number
Panel I.D.
User Password
Preheat Option
Load Accept Frequency Hz
Load Accept Voltage V
Starter Disengage Speed RPM
Number of Start Attempts Number
Generator Cool Down Time min.
Generator Warm Up Time sec.
Alarm Hold Off Time sec.
Start Attempt Pause Time sec.
Start Timer sec.
Preheat Timer sec.
Available Options: P1 = No Preheat, Before Start, Before and During Start
C1 = Direct Connection, Modem Connection, Modem Connection & Setup
Connection Mode (C1)
Direct Connection Only
Master Password
Required (Factory Only)
.05 to 300
30 to 200
000000 to 999999
000000 to 999999
(P1)
0to90
0 to 2000
0 to 4000
0to10
0 to 600
0 to 600
0to15
5 to 600
3to15
0to30
SYSTEM ALARM MENU
Parameter Value Units Active Type
Low Fuel Shutdown Alarm % Shutdown Alarm
Fuel Level Low Warning % Non-latching Alarm
Fuel Level High Warning % Non-latching Alarm
Under Freq. Hz Hold Off
Over Freq. Hz Hold Off
Under Voltage V Hold Off
Over Voltage V Hold Off
Engine Underspeed Alarm RPM Hold Off
Engine Overspeed Alarm RPM Immediate Shutdown Alarm
Battery Volts High Warning V Always Non-latching Alarm
Battery Volts Low Warning V Always Non-latching Alarm
Oil Temp. Shutdown Alarm Deg. F Shutdown Alarm
Oil Temp. Warning Deg. F Non-latching Alarm
Coolant Temp. Shutdown Alarm Deg. F Hold Off Shutdown Alarm
Coolant Temp. High Warning Deg. F Hold Off Non-latching Alarm
Coolant Temp. Low Warning Deg. F Always Non-latching Alarm
Oil Press. Shutdown Alarm PSI Hold Off Shutdown Alarm
Oil Press. Warning PSI Hold Off Non-latching Alarm
Available Options: A1 = Disable, Hold off, Immediate
A2 = Disable, Always
T1 = Shutdown Alarm, Latching Alarm, Non-latching Alarm, Status Message
0 to 100
0 to 100
0 to 100
0 to 100
0 to 100
0 to 2000
0 to 2000
0 to 4500
1000 to 4500
4to30
4to30
-5 to 275
-5 to 275
-5 to 275
-5 to 275
0 to 245
0 to 100
0 to 100
(A2)
(A2)
(A2)
(T1)
(T1)
(T1)
(T1)
(T1)
(A1)
(A1)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Generac Power Systems E and is the answer not in the manual?

Generac Power Systems E Specifications

General IconGeneral
BrandGenerac Power Systems
ModelE
CategoryControl Panel
LanguageEnglish

Related product manuals