37
Page
Number
39
39
39
40
40
40
40
41
41
42
42
42
43
44
44
45
Factory
Setting
5.0
5.0
000
000
004
60.0
0.0
10.0
6.0
000
000
005
0.0
000
0.5
1.5
Function Range/Code
0.1 - 999
0.1 - 999
000: Forward/Stop-Reverse/Stop
001: Run/Stop-Forward/Reverse
000: Forward Direction
001: Reverse Direction
001: 50Hz Constant Torque 004: 60Hz Constant Torque
002: 50Hz High Starting Torque 005: 60Hz High Starting Torque
003: 50Hz Variable Torque (HVAC) 006: 60Hz Variable Torque (HVAC)
1.0 - 200
0.0 - 200
1.0 - 200
1.0 - 200
000: Keypad Operation 001: External Run/Stop Contacts
000: Keypad 001: Potentiometer, 0 - 10V, 0 - 20mA
002: 4 - 20mA
001: 4 kHz 004: 7.2 kHz 007: 12 kHz 010: 16 kHz
002: 5 kHz 005: 8 kHz 008: 14.4 kHz
003: 6 kHz 006: 10 kHz 009: 15 kHz
0.0 - 10.0
000: Controlled Deceleration-to-Stop (with DC Injection Braking)
001: Coast-to-Stop
0.0 - 25.5
1.0 - 10.0
Function Description
Acceleration Time (Seconds)
Deceleration Time (Seconds)
External Forward-Stop-Reverse Control (See F10)
Motor Direction
Volts/Hz Pattern
1
Output Frequency Upper Limit(Hz)
1
Output Frequency Lower Limit (Hz)
Preset Speed #1 Frequency (Hz)
Jog Frequency (Hz)
Start/Stop Control (See F03)
Frequency Control Method
Switching Frequency (Code)
Volts/Hz Curve Modification (Torque Boost) (%)
Stop Method
DC Injection Brake Time (Seconds)
DC Injection Brake Start Frequency (Hz)
Function
Number
F01*
F02*
F03
F04*
F05
F06*
F07*
F08
F09
F10
F11
F12
F13
F14
F15
F16
TABLE 15 – PROGRAMMABLE FUNCTIONS SUMMARY LIST
Sec. VIII – Drive Operation (Cont.)
Table 15 continued on page 38.