Safety sensor close and open
5.2.3 Monitoring closing
X
Set the parameters:
à
s1
(safety closing) to
01
for “SIS” or to
02
for “SIS
and K”.
à
s3
(safety opening) to
00
for “no SIO”.
à
Te
(testing) to
02
for “testing with GND”.
1
SIS
11
1
GND
4
24VSEN
10
TST
-UB
+UB
COM
+
SIO
60 mA
Test
SIS
GC 342
BN
GN
YE
WH
PK
GY
BU
RD
1 Door transmission cable
5.3 Safety sensor GC334
à GC334 module, mat. no. 126410
à Accessories:
à GC334 interface, mat. no. 128306
à Spot nder, mat. no. 112321
à max. 6 modules in series
X
Follow the installation instructions.
5.3.1 Monitoring closing and opening
X
Set the parameters:
à
s1
(safety closing) to
01
for “SIS” or to
02
for “SIS
and K”.
à
s3
(safety opening) to
01
for “SIO”.
à
Te
(testing) to
02
for “testing with GND”.
X
Congure GC334 modules:
à Hinge side: DIP1 = ON
à Opposite hinge side: DIP1 = OFF
SIS
1
GND
11
SIS
10
TST
4
24VSENS
1
GND
13
SIO
10
TST
4
24VSENS
SIO
VT
PK
WH
YE
GN
-
+
BN
BU
-
+
RD
GC 334 Module BS
60mA
1
1 Door transmission cable