EasyManuals Logo

Grundfos CONTROL MPC User Manual

Grundfos CONTROL MPC
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
42
11.7.29 Analog inputs (4.3.8.1 to 4.3.8.7)
Fig. 70 Analog inputs
Description
In the displays 4.3.8.1 to 4.3.8.7, analog inputs can be set.
Each display is divided into three parts:
Setting of input signal, for instance 4-20 mA
Measured input value, for instance discharge pressure
Measuring range of the sensor/signal transmitter, for instance
0-16 bar.
Setting range
It is possible to set the following parameters in each display:
Not used
Range of input signal, 0-20 mA, 4-20 mA, 0-10 V
Measured input value
Sensor range.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Secondary functions with or , and press .
3. Mark Analog inputs with or , and press .
4. Select the analog input with or , and press .
5. Mark the setting of the analog input with or , and
activate it with .
The activation is indicated by a check mark in the box.
Factory setting
11.7.30 Analog inputs and measured value (4.3.8.1.1 to
4.3.8.7.1)
Fig. 71 Analog inputs and measured value
Description
In the display Analog inputs and measured value (4.3.8.1.1 to
4.3.8.7.1), a function can be related to the individual analog
inputs.
Setting range
It is possible to select one function per analog input. For further
details, see section 12. Measuring parameters.
Not used
0-100 % signal
Inlet pressure
Discharge pressure
External pressure
Differential pressure, pump
•Flow rate
Tank level, discharge side
Tank level, suction side
System pressure
Differential pressure, external
Tank precharge pressure
Differential pressure, inlet
Differential pressure, outlet
Return pipe temperature, external
Flow pipe temperature
Return pipe temperature
Differential temperature
Ambient temperature
Power, pump 1 to 6
Power, VFD.
Setting via control panel
1. Mark the Settings menu with .
2. Mark Secondary functions with or , and press .
3. Mark Analog inputs with or , and press .
4. Select the analog input with or , and press .
5. Set the range of the analog input with or , and press
.
The activation is indicated by a check mark.
6. Mark Measured input value with or , and press .
Now the display 4.3.8.1.1 appears.
7. Select the input with or , and press .
8. Press to return to display 4.3.8.1.
9. Set the minimum sensor value with or , and save with
.
10.Set the maximum sensor value with or , and save
with .
TM03 2357 4607
Note
If an analog input is deactivated, the display will
only show the top part, i.e. the setting of the
analog input.
If the input is activated, the middle part,
"Measured input value", will be shown. This
makes it possible to relate a function to the
analog input in another display. When the analog
input has been related to a function, CU 351 will
return to the display for setting of analog inputs.
Pressure boosting
Analog input Function
AI1 (CU 351) [51] Discharge pressure
Heating and cooling
Analog input Function
AI1 (CU 351) [51] These are selected in the start-up wizard
TM03 8973 4807

Table of Contents

Other manuals for Grundfos CONTROL MPC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CONTROL MPC and is the answer not in the manual?

Grundfos CONTROL MPC Specifications

General IconGeneral
BrandGrundfos
ModelCONTROL MPC
CategoryControl Systems
LanguageEnglish

Related product manuals