114
Proceed the are tube connecting operation to connect all the refrigerant tubes.
Dual wrenches must be used in the
connection of indoor unit tubing.
Mounting torque refers to the right table
Cutting and Enlarging
Vacuumizing
Open All Valves
Checkup for Air Leakage
Cutting or enlarging pipes should be proceeded
by installation personnel according to the
operating criterion if the tube is too long or are
opening is broken.
Vacuumize from the stop valve of outdoor units with
vacuum pump. Refrigerant sealed in indoor machine
is not allowed to use for vacuumization.
Open all the valves of outdoor units. [NB: oil
balancing stop valve must be shut up completely
when connected one master unit.]
Check if there is any leakage at the connecting part
and bonnet with hydrophone or soapsuds.
Connecting
1. Connecting circular terminals:
The connecting method of circular terminal is shown
in the Fig. Take off the screw, connect it to the terminal
tier after heading it through the ring at the end of the
lead and then tighten it.
2. Connecting straight terminals:
The connection methods for the circular terminals are
shown as follows: loosen the screw before putting the
line terminal into the terminal tier, tighten the screw
and conrm it has been clamped by pulling the line
gently.
3. Pressing connecting line:
After connecting line is completed, press the
connecting line with clips which should press on the
protective sleeve of the connecting line.
Outer diameter
of tubing (mm)
Mounting
torque (N.m)
Increase mounting
torque (N.m)
Φ6.35 11.8 (1.2kgf.m) 13.7 (1.4kgf.m)
Φ9.52 24.5 (2.5kgf.m) 29.4 (3.0kgf.m)
Φ12.7 49.0 (5.0kgf.m) 53.9 (5.5kgf.m)
Φ15.88 78.4 (8.0kgf.m) 98.0 (10.0kgf.m)
Connecting Procedures of Refrigerant Tubing
5.9.2 Electrical wiring
WARNING
Electrical construction should be made with specic mains circuit by the qualied personnel according to the
installation instruction. Electric shock and re may be caused if the capacity of power supply is not sufcient.
During arranging the wiring layout, specied cables should be used as the mains line, which accords with the
local regulations on wiring. Connecting and fastening should be performed reliably to avoid the external force of
cables from transmitting to the terminals. Improper connection or fastness may lead to burning or re accidents.
There must be the ground connection according to the criterion. Unreliable grounding may cause electrical
shocks. Do not connect the grounding line to the gas pipe, water pipe, lightening rod and telephone line.