441
Fresh Air Type
Indoor Unit
17.6 Electric characteristics
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker W: Fan motor rated output (W) FLA: Full load amps (A)
Notes:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.
Units Power supply Indoor fan motor Power input (W)
Model Phase FQY Voltage
Volt
range
MCA MFA Output (W) FLA Cooling Heating
AD482MPERA 1 50/60 220 198-242 3.25 10.4 265/270 2.6 560 560
AD722MPERA 1 50/60 220 198-242 5.6 18 326*2 2.25*2 730 730
AD962MPERA 1 50/60 220 198-242 5.6 18 326*2 2.25*2 870 870