189
Slim Duct Type
Indoor Unit
8.6 Electric characteristics
Units Power supply Indoor fan motor Power input (w)
Model Phase FQY Voltage Volt range MCA MFA Output (W) FLA Cooling Heating
AD052MSERA 1 50/60 220 198-242 0.24 0.76 23 0.19 56 56
AD072MSERA 1 50/60 220 198-242 0.24 0.76 23 0.19 56 56
AD092MSERA 1 50/60 220 198-242 0.24 0.76 23 0.19 56 56
AD122MSERA 1 50/60 220 198-242 0.38 1.2 23 0.3 56 56
AD162MSERA 1 50/60 220 198-242 0.59 1.88 51 0.47 65 65
AD182MSERA 1 50/60 220 198-242 0.38 1.2 44 0.3 80 80
AD242MSERA 1 50/60 220 198-242 0.59 2.12 55 0.53 117 117
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.