19
4-Way Cassette
Type Indoor Unit
2.6 Electric characteristics
Units Power supply Indoor fan motor Power input (w)
Model Phase FQY Voltage
Volt.
range
MCA MFA
Output
(W)
FLA Cooling Heating
AB052MCERA 1 50/60 220 198~242 0.5 1.6 40 0.4 80 80
AB072MCERA 1 50/60 220 198~242 0.5 1.6 40 0.4 80 80
AB092MCERA 1 50/60 220 198~242 0.5 1.6 40 0.4 80 80
AB122MCERA 1 50/60 220 198~242 0.5 1.6 40 0.4 80 80
AB162MCERA 1 50/60 220 198~242 0.5 1.6 40 0.4 80 80
AB182MCERA(C) 1 50/60 220 198~242 0.5 1.6 40 0.4 80 80
AB182MCERA 1 50/60 220 198~242 0.69 2.2 50 0.55 145 145
AB242MCERA 1 50/60 220 198~242 0.69 2.2 50 0.55 145 145
AB282MCERA 1 50/60 220 198~242 0.69 2.2 50 0.55 145 145
AB302MCERA 1 50/60 220 198~242 1.38 4.4 90 1.1 150 150
AB382MCERA 1 50/60 220 198~242 1.38 4.4 90 1.1 150 150
AB482MCERA 1 50/60 220 198~242 1.38 4.4 90 1.1 150 150
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker
Output: Fan motor rated output (w)
FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.