5.6 Electric characteristics
Unit Power supply Indoor fan motor Power input (W)
Model Phase Voltage FQY
Volt.
range
MCA MFA
Output
(W)
FLA Cooling Heating
AB072MBERA 1 220 50/60 198~242 0.5 1.6 35 0.4 90 90
AB092MBERA 1 220 50/60 198~242 0.5 1.6 35 0.4 90 90
AB122MBERA 1 220 50/60 198~242 0.5 1.6 35 0.4 90 90
AB162MBERA 1 220 50/60 198~242 0.5 1.6 35 0.4 110 110
AB182MBERA 1 220 50/60 198~242 0.5 1.6 35 0.4 110 110
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker
Output: Fan motor rated output (w)
FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.