16.6 Electric characteristics
Units Power supply Indoor fan motor Power input (w)
Model Phase FQY Voltage Volt range MCA MFA Output (W) FLA Cooling Heating
AD182MHERA 1ph 50/60 220 198~242 2.5 8 260 2 450 450
AD242MHERA 1ph 50/60 220 198~242 2.5 8 260 2 450 450
AD282MHERA 1ph 50/60 220 198~242 2.5 8 260 2 450 450
AD302MHERA 1ph 50/60 220 198~242 3 9.6 270 2.4 560 560
AD382MHERA 1ph 50/60 220 198~242 3 9.6 270 2.4 560 560
AD482MHERA 1ph 50/60 220 198~242 3 9.6 270 2.4 560 560
AD722MHERA 1ph 50/60 220 198~242 4.65 14.88 238*2 1.86*2 1100 1100
AD962MHERA 1ph 50/60 220 198~242 4.65 14.88 238*2 1.86*2 1100 1100
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker
Output: Fan motor rated output (w)
FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.