15.6 Electric characteristics
Units Power supply Indoor fan motor Power input (W)
Model Phase FQY Voltage Volt. range MCA MFA Output (W) FLA Cooling Heating
AD072MQERA 1 50/60 220 198~242 1.35 4.32 120 1.08 120 120
AD092MQERA 1 50/60 220 198~242 1.35 4.32 120 1.08 120 120
AD122MQERA 1 50/60 220 198~242 1.93 6.16 186 1.54 181 181
AD152MQERA 1 50/60 220 198~242 1.93 6.16 186 1.54 181 181
AD182MQERA 1 50/60 220 198~242 1.93 6.16 186 1.54 181 181
AD242MQERA 1 50/60 220 198~242 2.60 8.32 245 2.08 252.3 252.3
AD282MQERA 1 50/60 220 198~242 2.68 8.56 245 2.14 259.3 259.3
AD302MQERA 1 50/60 220 198~242 2.68 8.56 245 2.14 259.3 259.3
AD362MQERA 1 50/60 220 198~242 3.25  10.40 212 2.60 315.6 315.6
AD422MQERA 1 50/60 220 198~242 3.25  10.40 212 2.60 315.6 315.6
AD482MQERA 1 50/60 220 198~242 3.58  11.44 254 2.86 366.8 366.8
AD542MQERA 1 50/60 220 198~242 3.58  11.44 254 2.86 366.8 366.8
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Notes:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA.
4. Power supply uses the circuit breaker.