11.6 Electric characteristics
Units Power supply Indoor fan motor Power input (w)
Model Phase FQY Voltage Volt. range MCA MFA Output (W) FLA Cooling Heating
AD182MMERA 1 50/60 220 198-242 1.19 3.8 150 0.95 100 100
AD242MMERA 1 50/60 220 198-242 1.19 3.8 150 0.95 100 100
AD282MMERA 1 50/60 220 198-242 1.19 3.8 150 0.95 100 100
AD302MMERA 1 50/60 220 198-242 1.81 5.8 60/45 1.45 200 200
AD382MMERA 1 50/60 220 198-242 1.81 5.8 60/45 1.45 200 200
AD482MMERA 1 50/60 220 198-242 1.81 5.8 60/45 1.45 200 200
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.