18.6 Electric characteristics
Units Power supply Indoor fan motor Power input (w)
Model Voltage FQY Volt range MCA MFA Output (W) FLA Cooling Heating
AE072MLERA 220 50/60 198~242 0.68 2.16 33/37 0.54 110 110
AE092MLERA 220 50/60 198~242 0.68 2.16 33/37 0.54 110 110
AE122MLERA 220 50/60 198~242 0.68 2.16 33/37 0.54 110 110
AE162MLERA 220 50/60 198~242 1.1 3.4 63/70 0.85 150 150
AE182MLERA 220 50/60 198~242 1.1 3.4 63/70 0.85 150 150
AE242MLERA 220 50/60 198~242 1.1 3.4 63/70 0.85 150 150
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker
Output: Fan motor rated output (w)
FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.