EasyManua.ls Logo

Haier AB072MRERA - Electric Characteristics

Haier AB072MRERA
651 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
485
Console Type
Indoor Unit
19.6 Electric characteristics
Units Power supply Indoor fan motor Power input (w)
Model Phase FQY Voltage Volt range MCA MFA Output (W) FLA Cooling Heating
AF052MAERA 1 50/60 220 198~242 0.28 0.88 20/11 0.22 100 100
AF072MAERA 1 50/60 220 198~242 0.28 0.88 20/11 0.22 100 100
AF092MAERA 1 50/60 220 198~242 0.28 0.88 20/11 0.22 100 100
AF122MAERA 1 50/60 220 198~242 0.28 0.88 20/11 0.22 100 100
AF182MAERA 1 50/60 220 198~242 0.28 0.88 20/11 0.22 100 100
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker
Output: Fan motor rated output (w)
FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.

Table of Contents

Related product manuals