12.6 Electric characteristics
Units Power supply Indoor fan motor Power input (W)
Model Phase FQY Voltage Volt. range MCA MFA Output (W) FLA Cooling Heating
AD052MJERA 1 50/60 220 198~242 0.64 2.56 42 0.51 98 98
AD072MJERA 1 50/60 220 198~242 0.64 2.56 42 0.51 98 98
AD092MJERA 1 50/60 220 198~242 0.64 2.56 42 0.51 98 98
AD122MJERA 1 50/60 220 198~242 0.64 2.56 42 0.51 98 98
AD162MJERA 1 50/60 220 198~242 0.96 3.84 64 0.77 137 137
AD182MJERA 1 50/60 220 198~242 1.01 4.04 69 0.86 144 144
AD242MJERA 1 50/60 220 198~242 1.48 5.92 112 1.18 187 187
AD282MJERA 1 50/60 220 198~242 1.48 5.92 112 1.18 187 187
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Notes:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA.
4. Power supply uses the circuit breaker.