Indoor Unit (AD*MZERA)
13.6 Electric characteristic
Units Power supply Indoor fan motor Power input (w)
Model Phase FQY Voltage Volt range MCA MFA Output (W) FLA Cooling Heating
AD182MZERA 1 50/60 220 198~242 2 6.4 88 1.6 210 210
AD242MZERA 1 50/60 220 198~242 2 6.4 88 1.6 210 210
AD282MZERA 1 50/60 220 198~242 2 6.4 88 1.6 210 210
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker
Output: Fan motor rated output (w)
FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.