160
7.6 Electric characteristics
Units Power supply Indoor fan motor Power input (W)
Model Phase FQY Voltage
Volt.
range
MCA MFA
Output 
(W)
FLA Cooling Heating
AC092MCERA 1 50/60 220 198~242 0.64 2.04 28 0.51 100 100
AC122MCERA 1 50/60 220 198~242 0.64 2.04 28 0.51 100 100
AC162MCERA 1 50/60 220 198~242 0.64 2.04 28 0.51 100 100
AC182MCERA 1 50/60 220 198~242 0.64 2.04 28 0.51 100 100
AC242MCERA 1 50/60 220 198~242 0.64 2.04 28 0.51 100 100
AC282MFERA 1 50/60 220 198~242 2.51 8.04 105 2.01 200 200
AC302MFERA 1 50/60 220 198~242 2.51 8.04 105 2.01 200 200
AC382MFERA 1 50/60 220 198~242 2.51 8.04 105 2.01 400 400
AC482MFERA 1 50/60 220 198~242 2.51 8.04 105 2.01 400 400
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Notes: 
1. Voltage range
    The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%. 
3. MCA=1.25*FLA MFA≤4*FLA.
4. Power supply uses the circuit breaker.