529
High Wall Type
Indoor Unit (N platform)
21.6 Electric characteristics
Units Power supply Indoor fan motor Power input (W)
Model Phase FQY Voltage
Volt.
range
MCA MFA
Output
(W)
FLA Cooling Heating
AS052MNERA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
AS072MNERA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
AS092MNERA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
AS122MNERA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
AS162MNERA 1 50/60 220 198~242 0.24 0.76 40 0.19 57 57
AS182MNERA 1 50/60 220 198~242 0.24 0.76 40 0.19 57 57
AS242MNERA 1 50/60 220 198~242 0.24 0.76 40 0.19 57 57
AS282MNERA 1 50/60 220 198~242 0.4 1.28 70 0.32 99 99
AS302MNERA 1 50/60 220 198~242 0.4 1.28 70 0.32 99 99
AS052MFERA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
AS072MFERA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
AS092MFERA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
AS122MFERA 1 50/60 220 198~242 0.18 0.56 30 0.14 43 43
AS162MFERA 1 50/60 220 198~242 0.24 0.76 40 0.19 57 57
AS182MFERA 1 50/60 220 198~242 0.24 0.76 40 0.19 57 57
AS242MFERA 1 50/60 220 198~242 0.24 0.76 40 0.19 57 57
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Notes:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA.
4. Power supply uses the circuit breaker.