EasyManua.ls Logo

Haier AB072MRERA - Electric Characteristics

Haier AB072MRERA
651 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
243
Low ESP Duct
Type Indoor Unit
10.6 Electric characteristics
Units Power supply Indoor fan motor Power input (w)
Model Phase FQY Voltage Volt. range MCA MFA Output (W) FLA Cooling Heating
AD072MLERA 1 50/60 220 198-242 0.31 1 12 0.25 30 30
AD092MLERA 1 50/60 220 198-242 0.31 1 12 0.25 30 30
AD122MLERA 1 50/60 220 198-242 0.44 1.2 12 0.35 45 45
AD162MLERA 1 50/60 220 198-242 0.4 1.28 14 0.32 50 50
AD182MLERA 1 50/60 220 198-242 1.25 4 33 1 110 110
AD242MLERA 1 50/60 220 198-242 1.25 4 37 1 110 110
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Note:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA
4. Power supply uses the circuit breaker.

Table of Contents

Related product manuals