203
Slim Duct Type 
Indoor Unit
8.9.3 Test run 
Before Test Run
Ways of Test Run
Before switching it on, test the supply terminal tier (L, N terminals) and grounding points with 500V megaohm meter 
and check if the resistance is above 1MΩ. It can't be operated if it is below 1MΩ. 
Connect it to the power supply of outdoor units to energize the heating belt of the compressor. To protect the 
compressor at startup, power it on 12 hours prior to the operation.
Check if the arrangements of the drainpipe and connection line are correct.
The drainpipe shall be placed at the lower part while the connection line placed at the upper part. Heat preservation 
measures should be taken such as winding the drainpipe esp. in the indoor units with heating insulating materials.
The drain pipe should be made a slope type to avoid protruding at the upper part and concaving at the lower part 
on the way.
Checkup of Installation
 Check if the mains voltage is matching   
 Check if there is air leakage at the piping joints  
 Check if the connections of mains power and 
    indoor & outdoor units are correct     
 Check if the serial numbers of terminals are matching 
 Check if the installation place meets the requirement    
 Check if there is too much noise    
 Check if the connecting line is fastened   
 Check if the connectors for tubing are heat insulated    
 Check if the water is drained to the outside   
 Check if the indoor units are positioned
Do ask the installation personnel to make a test run. Take the testing procedures according to the manual and 
check if the temperature regulator works properly.
When the machine fails to start due to the room temperature, the following procedures can be taken to do the 
compulsive running. The function is not provided for the type with remote control.
 ■ Set the wired controller to cooling/heating mode, press "ON/OFF" button for 5 seconds to enter into the 
compulsive cooling/heating mode. Repress "ON/OFF" button to quit the compulsive running and stop the 
operation of the air conditioner.
                            Setting 
                              mode
Socket/dip 
switch
Wired control master unit Wired control slave unit  Remote control
SW01-[2][3][4] All OFF [0][0][1] All OFF
CN21 socket Null Null
Connect to remote 
receiver
Terminal block (control)
A, B, C connect with wired 
controller
B, C connect with wired 
controller
A, B, C Null