HI 6600 Series Modular Sensor System User Guide
Page | 125
4: WRITE NONVOL CMD. Write a #4 to the command register to save parameters in
non-volatile
memory.
o No Error Codes
5: CMD: Reserved
o No Error Codes
6: WEIGHT SAMPLE CMD: Write a #6 to the command register to run the Weigh
Sample command to set up the calibration of the Counts (if enabled).
o Status Error code 1 (motion)
o Status error code 2 (A/D error)
0x64 (100 decimal): CAL LOW CMD. Write a 0x64 hex to the command register to
perform the
low step of a traditional calibration. The status register will read 0 if this
command succeeds:
o
Calibration_Fail 1
o
Calibration_Fail_Motion 3
o
Calibration_Fail_Adc_Error 4
0x65 (101decimal): CAL HIGH CMD. Write a 0x65 hex to the command register to
perform the
high step of a traditional calibration.
o
Calibration_Fail 1
o
Calibration_Fail_Motion 3
o
Calibration_Fail_Adc_Error 4
o HardcalFailCounts 8: not enough counts between hard cal hi and hard cal lo
0x66 (102 decimal): C2 CAL CMD. Write a 0x66 hex to the command register to
perform a C2
calibration.
o
Calibration_Fail 1
o
Calibration_Fail_Motion 3
o
Calibration_Fail_Adc_Error 4
o
Calibration_Fail_Noc2 5
o
Calibration_Fail_C2capeq 6
o
Calibration_Fail_C2clones 7
0x1000 (4096 decimal): WRITE INTEGER CMD. Set the value of an integer
parameter.
Write 0x1000 in the command register 0, the parameter ID number in
registers 2, 3 and the
desired value in registers 4, 5.
o No Error Codes
0x1001 (4097 decimal): WRITE FLOAT CMD. Set the value of a floating point
parameter.
Write 0x1001 in the command register 0, the parameter ID number in
registers 2, 3 and the
desired float value in registers 4, 5.
Failure 1
TooHigh -1 : value is above legal limit
TooLow -2 : value is below legal limit
ErrorNotFound 0x8000 : parameter id not found