HDL KNX / EIB Switch Actuators
_____________________________________________________________________________________
Guangzhou Hedong Electronic Co.,Ltd (HDL)
www.hdlchina.com 18/58
Options: No
Yes
No: Not alarm
Yes: Alarm
>>:--Alarm when counter our(10..10000000)
This parameter set the ON alarm overflow time.counter
Options: 10..10000000
>>:--Alarm telegram interval when counter out(1..255s)
This parameter is set ON counter overflow alarm interval.
Options: 1..255s
>>:--Alarm telegram number(1..255,0-unlimited)
This parameter set the ON counter overflow alarm number.
Options:0-unlimited
1..255
---The switch state on bus voltage fail
When bus voltage failure and the function will be executed. Three
choices will be available as following:
Options: Unchange
ON
OFF
Unchange: The channel switch position unchanged after bus voltage
failure
ON: The channel position will be switch ON after bus voltage failure
OFF: The channel position switch OFF after bus voltage failure
---The operation of switch after bus voltage recovery
When power on and the bus voltage recovery, This function will be
executed. four choices will be available as following:
Options: Unchange
Recovery
ON
OFF
Unchange: The channel switch position unchanged after bus voltage
recovery.
Recovery: After bus voltage recovery, The channel switch position
will be back to the state of the power-down previous.
ON: The channel position will switch ON after bus voltage recovery.