EMC and immunity
Note: You will find detailed information on the certificates and declara-
tions applying to your device in a separate overview.
See table 2 on page 14.
Stability Standard appli-
cations
Substation
applications
IEC 60068-2-6, test Fc Vibration — 2 Hz ... 9 Hz with
0.12 in. (3 mm)
amplitude
5 Hz ... 8.4 Hz
with 0.14 in.
(3.5 mm) ampli-
tude
5 Hz ... 8.4 Hz
with 0.14 in.
(3.5 mm) ampli-
tude
8.4 Hz ... 150 Hz
with 1 g
9 Hz ... 200 Hz
with 1 g
— 200 Hz ... 500 Hz
with 1.5 g
IEC 60068-2-27, test Ea Shock 15 g at 11 ms 15 g at 11 ms
EMC interference emis-
sion
Standard appli-
cations
Substation
applications
Radiated emission
EN 55022 Class A Class A
GL Guidelines — —
FCC 47 CFR Part 15 Class A Class A
EN 61000-6-4 Fulfilled Fulfilled
Conducted emission
EN 55022 AC and DC supply connec-
tions
Class A Class A
GL Guidelines AC and DC supply connec-
tions
——
FCC 47 CFR Part 15 AC and DC supply connec-
tions
Class A Class A
EN 61000-6-4 AC and DC supply connec-
tions
Fulfilled Fulfilled
EN 55022 Telecommunication
connections
Class A Class A
EN 61000-6-4 Telecommunication
connections
Fulfilled Fulfilled