EasyManuals Logo

Hirschmann RSP 20 User Manual

Hirschmann RSP 20
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
Installation RSP 20/25/30/35
Release
08
08/2014
43
EMC and immunity
Note: You will find detailed information on the certificates and declara-
tions applying to your device in a separate overview.
See table 2 on page 14.
Stability Standard appli-
cations
Substation
applications
IEC 60068-2-6, test Fc Vibration 2 Hz ... 9 Hz with
0.12 in. (3 mm)
amplitude
5 Hz ... 8.4 Hz
with 0.14 in.
(3.5 mm) ampli-
tude
5 Hz ... 8.4 Hz
with 0.14 in.
(3.5 mm) ampli-
tude
8.4 Hz ... 150 Hz
with 1 g
9 Hz ... 200 Hz
with 1 g
200 Hz ... 500 Hz
with 1.5 g
IEC 60068-2-27, test Ea Shock 15 g at 11 ms 15 g at 11 ms
EMC interference emis-
sion
Standard appli-
cations
Substation
applications
Radiated emission
EN 55022 Class A Class A
GL Guidelines
FCC 47 CFR Part 15 Class A Class A
EN 61000-6-4 Fulfilled Fulfilled
Conducted emission
EN 55022 AC and DC supply connec-
tions
Class A Class A
GL Guidelines AC and DC supply connec-
tions
——
FCC 47 CFR Part 15 AC and DC supply connec-
tions
Class A Class A
EN 61000-6-4 AC and DC supply connec-
tions
Fulfilled Fulfilled
EN 55022 Telecommunication
connections
Class A Class A
EN 61000-6-4 Telecommunication
connections
Fulfilled Fulfilled